Voltage Drop Calculator

View results · 6.34 V

Circuit and cable

Circuit type
Conductor
Wire sizes

Cross-section about 3.31 mm².

Conductor type
Length unit

Enter the one-way length from the source to the load. Current is the load current in amperes.

Result

Voltage drop
Percentage drop
Voltage at the load
113.66 V
Conductor resistance
1.98 Ω/1000 ft
Power lost in the cable
101.4 W
Above the 5% combined limit recommended by NEC informational notes. Consider a larger conductor or a shorter run.
  • Smallest size for at most 3%: 8 AWG
  • Smallest size for at most 5%: 10 AWG
Vd=2×0.1×16×1.98≈6.34 VV_d=2\times0.1\times16\times1.98\approx6.34\,\text{V}
VdV=6.34120≈5.28%\frac{V_d}{V}=\frac{6.34}{120}\approx5.28\%

Resistance from NEC Chapter 9, Table 8 (DC, uncoated copper or aluminum at 75 °C).

About this tool

Every wire has resistance, so part of the voltage is lost along the cable before it reaches the load. On long runs this voltage drop can make motors run hot, lights dim and electronics misbehave, and it wastes energy as heat. The drop grows with the current and the length and falls as the conductor gets thicker, which is why long circuits often need a larger wire than the ampacity tables alone suggest.

In the United States, informational notes in the National Electrical Code recommend sizing conductors so that the drop is no more than 3% on a branch circuit or feeder and no more than 5% for both together. These notes are recommendations for efficient operation, not mandatory requirements, although some local codes and specifications make them binding.

How it works

Choose the circuit type and enter the source voltage and the load current. Then pick copper or aluminum, the wire size in AWG/kcmil or mm², and the one-way length of the run from the source to the load. The calculator shows the voltage drop in volts and as a percentage, the voltage that reaches the load and the power lost as heat in the cable.

For single-phase AC and DC circuits the current flows out and back, so the drop is Vd=2 L I RV_d = 2\,L\,I\,R. For a balanced three-phase circuit, with the line-to-line voltage, it is Vd=3 L I RV_d = \sqrt{3}\,L\,I\,R. R is the conductor resistance per unit length at 75 °C: NEC Chapter 9, Table 8 values for AWG and kcmil, and IEC 60228 values corrected to 75 °C for mm². The calculator also finds the smallest size of the same material that keeps the drop within 3% and 5%.

Vd,1∼=2 L I R,Vd,3∼=3 L I RV_{d,1\sim}=2\,L\,I\,R,\qquad V_{d,3\sim}=\sqrt{3}\,L\,I\,R

Example

A 120 V, 16 A load is fed with 12 AWG stranded copper, 100 ft from the panel. Table 8 gives 1.98 Ω per 1000 ft, so Vd=2×0.1×16×1.98≈6.34V_d = 2 \times 0.1 \times 16 \times 1.98 \approx 6.34 V. That is 6.34/120≈5.3%6.34 / 120 \approx 5.3\%, leaving about 113.7 V at the load. Upsizing to 10 AWG (1.24 Ω per 1000 ft) cuts the drop to about 3.97 V or 3.3%, and 8 AWG brings it below 3%.

For a 230 V circuit with 2.5 mm² copper over 30 m at 16 A, the resistance at 75 °C is about 9.01 Ω/km, so Vd=2×0.03×16×9.01≈8.65V_d = 2 \times 0.03 \times 16 \times 9.01 \approx 8.65 V, or 3.8%.

Conductor resistance tables

DC resistance at 75 °C, NEC Chapter 9, Table 8 (stranded / solid)

SizeArea (mm²)Copper (Ω/1000 ft)Aluminum (Ω/1000 ft)
18 AWG0.827.95 / 7.7713.1 / 12.8
16 AWG1.314.99 / 4.898.21 / 8.05
14 AWG2.083.14 / 3.075.17 / 5.06
12 AWG3.311.98 / 1.933.25 / 3.18
10 AWG5.261.24 / 1.212.04 / 2
8 AWG8.370.778 / 0.7641.28 / 1.26
6 AWG13.30.4910.808
4 AWG21.150.3080.508
3 AWG26.670.2450.403
2 AWG33.630.1940.319
1 AWG42.410.1540.253
1/0 AWG53.480.1220.201
2/0 AWG67.430.09670.159
3/0 AWG85.030.07660.126
4/0 AWG107.220.06080.1
250 kcmil126.680.05150.0847
300 kcmil152.010.04290.0707
350 kcmil177.350.03670.0605
400 kcmil202.680.03210.0529
500 kcmil253.350.02580.0424
600 kcmil304.020.02140.0353
700 kcmil354.70.01840.0303
750 kcmil380.030.01710.0282
800 kcmil405.370.01610.0265
900 kcmil456.040.01430.0235
1000 kcmil506.710.01290.0212

Maximum DC resistance, IEC 60228 class 2 conductors, and the value at 75 °C

Size (mm²)Copper, 20 °C (Ω/km)Copper, 75 °C (Ω/km)Aluminum, 20 °C (Ω/km)Aluminum, 75 °C (Ω/km)
0.53643.8——
0.7524.529.8——
118.122——
1.512.114.7——
2.57.419.01——
44.615.61——
63.083.75——
101.832.233.083.76
161.151.41.912.33
250.7270.8841.21.47
350.5240.6370.8681.06
500.3870.4710.6410.783
700.2680.3260.4430.541
950.1930.2350.320.391
1200.1530.1860.2530.309
1500.1240.1510.2060.252
1850.09910.1210.1640.2
2400.07540.09170.1250.153

Solid values apply to 18–8 AWG. IEC 60228 values are corrected from 20 °C with the standard's temperature formula; class 2 aluminium conductors start at 10 mm².

Assumptions and limits

The calculation uses DC resistance at a conductor temperature of 75 °C and ignores inductive reactance and power factor. That is accurate for DC and for AC circuits with smaller conductors, but for large conductors on AC, especially in steel conduit, the actual drop can be higher; NEC Chapter 9, Table 9 gives AC impedance values for those cases. Three-phase results assume a balanced load. IEC 60228 values are the maximum resistance the standard allows, so real cables are usually slightly better.

Voltage drop is only one part of conductor sizing. The wire must also have enough ampacity for the load, the right insulation and protection, and comply with local electrical codes. Have electrical work checked by a qualified electrician.

Frequently asked questions

What is an acceptable voltage drop?

NEC informational notes recommend a maximum of 3% on a branch circuit or feeder and 5% for feeder and branch circuit combined. Many European installation rules use similar limits of 3% for lighting and 5% for other uses.

Should I use the one-way or the round-trip length?

Enter the one-way distance from the source to the load. The formulas already account for the return path: the factor 2 for single-phase and DC circuits, and 3\sqrt{3} for three-phase circuits.

Why does aluminum wire have more voltage drop than copper?

Aluminum has about 61% of the conductivity of copper, so an aluminum conductor needs about two AWG sizes larger to have the same resistance and voltage drop.

How can I reduce voltage drop?

Use a larger conductor, shorten the run, reduce the current or raise the supply voltage. Doubling the voltage for the same power halves the current and cuts the percentage drop to a quarter.

Is the 3% voltage drop rule mandatory?

Not in the NEC in general: the 3% and 5% figures appear in informational notes, which are advisory. Some specific articles, energy codes and project specifications do set binding limits, so check the requirements that apply to your installation.

Link with your values

Add these parameters to this page’s address to open it with the values filled in, for example to share a calculation or to link to it from an AI assistant. The result is calculated in the browser: the page HTML shows an example for the default values, and the tool sets the data-url-params attribute once the link’s values are applied.

ParameterValueIf omitted
circuitCircuit typeone of: single_phase, three_phase, dcdefault single_phase
voltage_vSource voltagenumber; allowed > 0 – 1000000required
current_aLoad currentnumber; allowed > 0 – 100000required
materialConductorone of: copper, aluminumdefault copper
wire_size_awgWire sizeone of: 18, 16, 14, 12, 10, 8, 6, 4, 3, 2, 1, 1/0, 2/0, 3/0, 4/0, 250, 300, 350, 400, 500, 600, 700, 750, 800, 900, 1000default 12
wire_size_mm2Wire sizeone of: 0.5, 0.75, 1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240optional
strandingConductor typeone of: stranded, soliddefault stranded
one_way_length_ftOne-way lengthnumber; any unit in the name: _mm, _cm, _m, _km, _in, _ft, _yd, _mi, _nmi; allowed > 0 – 3280839.8950131233 ftrequired

Examples

  • ?circuit=single_phase&voltage_v=240&current_a=30&material=copper&wire_size_awg=10&one_way_length_ft=75
  • ?circuit=three_phase&voltage_v=400&current_a=32&wire_size_mm2=6&one_way_length_m=50

Write decimals with a point. Encode a space as %20, + as %2B, # as %23 and & as %26.

Result elements: [data-result-block="voltage-drop"]