About this tool
Every wire has resistance, so part of the voltage is lost along the cable before it reaches the load. On long runs this voltage drop can make motors run hot, lights dim and electronics misbehave, and it wastes energy as heat. The drop grows with the current and the length and falls as the conductor gets thicker, which is why long circuits often need a larger wire than the ampacity tables alone suggest.
In the United States, informational notes in the National Electrical Code recommend sizing conductors so that the drop is no more than 3% on a branch circuit or feeder and no more than 5% for both together. These notes are recommendations for efficient operation, not mandatory requirements, although some local codes and specifications make them binding.
How it works
Choose the circuit type and enter the source voltage and the load current. Then pick copper or aluminum, the wire size in AWG/kcmil or mm², and the one-way length of the run from the source to the load. The calculator shows the voltage drop in volts and as a percentage, the voltage that reaches the load and the power lost as heat in the cable.
For single-phase AC and DC circuits the current flows out and back, so the drop is . For a balanced three-phase circuit, with the line-to-line voltage, it is . R is the conductor resistance per unit length at 75 °C: NEC Chapter 9, Table 8 values for AWG and kcmil, and IEC 60228 values corrected to 75 °C for mm². The calculator also finds the smallest size of the same material that keeps the drop within 3% and 5%.
Example
A 120 V, 16 A load is fed with 12 AWG stranded copper, 100 ft from the panel. Table 8 gives 1.98 Ω per 1000 ft, so V. That is , leaving about 113.7 V at the load. Upsizing to 10 AWG (1.24 Ω per 1000 ft) cuts the drop to about 3.97 V or 3.3%, and 8 AWG brings it below 3%.
For a 230 V circuit with 2.5 mm² copper over 30 m at 16 A, the resistance at 75 °C is about 9.01 Ω/km, so V, or 3.8%.
Conductor resistance tables
DC resistance at 75 °C, NEC Chapter 9, Table 8 (stranded / solid)
| Size | Area (mm²) | Copper (Ω/1000 ft) | Aluminum (Ω/1000 ft) |
|---|---|---|---|
| 18 AWG | 0.82 | 7.95 / 7.77 | 13.1 / 12.8 |
| 16 AWG | 1.31 | 4.99 / 4.89 | 8.21 / 8.05 |
| 14 AWG | 2.08 | 3.14 / 3.07 | 5.17 / 5.06 |
| 12 AWG | 3.31 | 1.98 / 1.93 | 3.25 / 3.18 |
| 10 AWG | 5.26 | 1.24 / 1.21 | 2.04 / 2 |
| 8 AWG | 8.37 | 0.778 / 0.764 | 1.28 / 1.26 |
| 6 AWG | 13.3 | 0.491 | 0.808 |
| 4 AWG | 21.15 | 0.308 | 0.508 |
| 3 AWG | 26.67 | 0.245 | 0.403 |
| 2 AWG | 33.63 | 0.194 | 0.319 |
| 1 AWG | 42.41 | 0.154 | 0.253 |
| 1/0 AWG | 53.48 | 0.122 | 0.201 |
| 2/0 AWG | 67.43 | 0.0967 | 0.159 |
| 3/0 AWG | 85.03 | 0.0766 | 0.126 |
| 4/0 AWG | 107.22 | 0.0608 | 0.1 |
| 250 kcmil | 126.68 | 0.0515 | 0.0847 |
| 300 kcmil | 152.01 | 0.0429 | 0.0707 |
| 350 kcmil | 177.35 | 0.0367 | 0.0605 |
| 400 kcmil | 202.68 | 0.0321 | 0.0529 |
| 500 kcmil | 253.35 | 0.0258 | 0.0424 |
| 600 kcmil | 304.02 | 0.0214 | 0.0353 |
| 700 kcmil | 354.7 | 0.0184 | 0.0303 |
| 750 kcmil | 380.03 | 0.0171 | 0.0282 |
| 800 kcmil | 405.37 | 0.0161 | 0.0265 |
| 900 kcmil | 456.04 | 0.0143 | 0.0235 |
| 1000 kcmil | 506.71 | 0.0129 | 0.0212 |
Maximum DC resistance, IEC 60228 class 2 conductors, and the value at 75 °C
| Size (mm²) | Copper, 20 °C (Ω/km) | Copper, 75 °C (Ω/km) | Aluminum, 20 °C (Ω/km) | Aluminum, 75 °C (Ω/km) |
|---|---|---|---|---|
| 0.5 | 36 | 43.8 | — | — |
| 0.75 | 24.5 | 29.8 | — | — |
| 1 | 18.1 | 22 | — | — |
| 1.5 | 12.1 | 14.7 | — | — |
| 2.5 | 7.41 | 9.01 | — | — |
| 4 | 4.61 | 5.61 | — | — |
| 6 | 3.08 | 3.75 | — | — |
| 10 | 1.83 | 2.23 | 3.08 | 3.76 |
| 16 | 1.15 | 1.4 | 1.91 | 2.33 |
| 25 | 0.727 | 0.884 | 1.2 | 1.47 |
| 35 | 0.524 | 0.637 | 0.868 | 1.06 |
| 50 | 0.387 | 0.471 | 0.641 | 0.783 |
| 70 | 0.268 | 0.326 | 0.443 | 0.541 |
| 95 | 0.193 | 0.235 | 0.32 | 0.391 |
| 120 | 0.153 | 0.186 | 0.253 | 0.309 |
| 150 | 0.124 | 0.151 | 0.206 | 0.252 |
| 185 | 0.0991 | 0.121 | 0.164 | 0.2 |
| 240 | 0.0754 | 0.0917 | 0.125 | 0.153 |
Solid values apply to 18–8 AWG. IEC 60228 values are corrected from 20 °C with the standard's temperature formula; class 2 aluminium conductors start at 10 mm².
Assumptions and limits
The calculation uses DC resistance at a conductor temperature of 75 °C and ignores inductive reactance and power factor. That is accurate for DC and for AC circuits with smaller conductors, but for large conductors on AC, especially in steel conduit, the actual drop can be higher; NEC Chapter 9, Table 9 gives AC impedance values for those cases. Three-phase results assume a balanced load. IEC 60228 values are the maximum resistance the standard allows, so real cables are usually slightly better.
Voltage drop is only one part of conductor sizing. The wire must also have enough ampacity for the load, the right insulation and protection, and comply with local electrical codes. Have electrical work checked by a qualified electrician.
Frequently asked questions
What is an acceptable voltage drop?
NEC informational notes recommend a maximum of 3% on a branch circuit or feeder and 5% for feeder and branch circuit combined. Many European installation rules use similar limits of 3% for lighting and 5% for other uses.
Should I use the one-way or the round-trip length?
Enter the one-way distance from the source to the load. The formulas already account for the return path: the factor 2 for single-phase and DC circuits, and for three-phase circuits.
Why does aluminum wire have more voltage drop than copper?
Aluminum has about 61% of the conductivity of copper, so an aluminum conductor needs about two AWG sizes larger to have the same resistance and voltage drop.
How can I reduce voltage drop?
Use a larger conductor, shorten the run, reduce the current or raise the supply voltage. Doubling the voltage for the same power halves the current and cuts the percentage drop to a quarter.
Is the 3% voltage drop rule mandatory?
Not in the NEC in general: the 3% and 5% figures appear in informational notes, which are advisory. Some specific articles, energy codes and project specifications do set binding limits, so check the requirements that apply to your installation.
Link with your values
Add these parameters to this page’s address to open it with the values filled in, for example to share a calculation or to link to it from an AI assistant. The result is calculated in the browser: the page HTML shows an example for the default values, and the tool sets the data-url-params attribute once the link’s values are applied.
| Parameter | Value | If omitted |
|---|---|---|
circuitCircuit type | one of: single_phase, three_phase, dc | default single_phase |
voltage_vSource voltage | number; allowed > 0 – 1000000 | required |
current_aLoad current | number; allowed > 0 – 100000 | required |
materialConductor | one of: copper, aluminum | default copper |
wire_size_awgWire size | one of: 18, 16, 14, 12, 10, 8, 6, 4, 3, 2, 1, 1/0, 2/0, 3/0, 4/0, 250, 300, 350, 400, 500, 600, 700, 750, 800, 900, 1000 | default 12 |
wire_size_mm2Wire size | one of: 0.5, 0.75, 1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240 | optional |
strandingConductor type | one of: stranded, solid | default stranded |
one_way_length_ftOne-way length | number; any unit in the name: _mm, _cm, _m, _km, _in, _ft, _yd, _mi, _nmi; allowed > 0 – 3280839.8950131233 ft | required |
Examples
?circuit=single_phase&voltage_v=240¤t_a=30&material=copper&wire_size_awg=10&one_way_length_ft=75?circuit=three_phase&voltage_v=400¤t_a=32&wire_size_mm2=6&one_way_length_m=50
Write decimals with a point. Encode a space as %20, + as %2B, # as %23 and & as %26.
Result elements: [data-result-block="voltage-drop"]